Specifications
Each pole of the circuit breaker power consumption
| Electrical Features | Standard | 
 | IEC/EN 60898-1 | 
| Rated current In | A | 1,2,4,6,10,16,20,25,32,40,50,63 | |
| Poles | P | 1,2,3,4 | |
| Rated voltage Ue | V | AC 240/415 | |
| Insulation voltage Ui | V | 500 | |
| Rated frequency | Hz | 50/60 | |
| Rated breaking capacity | A | 3000,4500(2~40A/6000) | |
| Rated impulse with stand voltage(1.2/50) Uimp | V | 4000 | |
| Dielectric test voltage at ind. Frqu, for 1 min | KV | 2 | |
| Pollution degree | 
 | 2 | |
| Thermo-magnetic release characteristic | 
 | B,C,D | |
| Electrical life | T | 4000 | |
| Mechanical life | T | 10000 | |
| Protection degree | 
 | IP20 | |
| Reference temperature for | ℃ | 30 | |
| Setting of thermal element | 
 | ||
| Ambient temperature(with daily average ≤35℃) | ℃ | -5~+40(Special application please refer to temperature compensation correction) | |
| Storage temperature | ℃ | -25~+70 | |
| Installation | Terminal connection type | 
 | Cable/Pin type busbar/U type busbar | 
| Terminal size top/bottom for cable | mm2 | 25 | |
| AWG | 18-3 | ||
| Terminal size top/bottom for busbar | mm2 | 25 | |
| AWG | 18-3 | ||
| N*m | 2 | ||
| In-Ibs. | 18 | ||
| Mounting | 
 | ||
| Connection | 
 | 
Temperature derating
Please refer to table below for temperature compensation correction
| Rated Current In(A) | Temperature compensation coefficient under various operating temperature | ||||||||
| -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 55℃ | 60℃ | |
| 1-6 | 1.20 | 1.14 | 1.09 | 1.05 | 1.00 | 0.96 | 0.80 | 0.75 | 0.70 | 
| 10-32 | 1.18 | 1.12 | 1.08 | 1.04 | 1.00 | 0.96 | 0.92 | 0.88 | 0.84 | 
| 40-60 | 1.16 | 1.12 | 1.07 | 1.03 | 1.00 | 0.97 | 0.87 | 0.83 | 0.80 |