We not only will try our best to offer excellent services to every customer, but also are ready to receive any suggestion offered by our customers for Self Locking Cable Tie , Cable Distribution Box , Injection Molding Machine , Welcome to visit our firm and factory. Be sure to come to feel free to get in touch with us in case you need any additional assistance.
Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai Detail:

Connection

The RST 25 can be connected as following in the installation diagram:
FlG1: Connection of the relay before operation.
When the relay is connected as in FIG 1, the three yellow LED’s L1,L2 and L3 light up when the power supply A1 phase L, the A2 Neutral, and the three phases”L1,”L2″and”L3″are properly connected.
If there is no under of overvoltage, phase failure of phase sequence, the green LED lights up,(terminals 11 and 14 are closed ) and the relay is ready for operation.
FIG2: Connection of the relay after operation.
When the relay is connected as in FIG 2,(the power supply Al phase L, the A2 Neutral are properly connected) after operation, the three phases”L1″,”L2″and”L3″are connected, andthere is no under of overvoltage, phase falure, phase sequence, the green LED lights up(terminals 11 and
14are closed) and the relay is ready for self retaining.
It is also possible to connect the power supply after operation in FIG2.
By both FIG’s 1 and 2, the terminal “PE”must be grounded.

Undervoltage
The desired undervoltage limit can be adjusted down to -25% UN.

Overvoltage
The desired overvoltage limit can be adjusted up to +25% UN.

Asymmetry
When adjusting over-and undervoltage limit, the asymmetric limit is also adjusted.

Time Delay
The switch off time can be adjusted by the potentiometer “Time’ Delay”from 0.1….5 seconds. With this function it is possible to adjust the time for the identification of the failure.

Contactor Control
If a phase fails during operation at load or one of the contacts of the contactor or circuit breaker is defect,(contact bounce or scorched contacts), RST 25 recognizes the failure, and also the feedback voltage, and switches off depending on the setting of “Time Delay”
The RST 25 controls the phase shift. If there is a phase failure during operation the angle from the feedback voltage is 30° and the RST 25 recognizes this failure.


Product detail pictures:

Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai detail pictures


Related Product Guide:

We are going to make every single effort for being excellent and excellent, and accelerate our ways for standing while in the rank of international top-grade and high-tech enterprises for Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai , The product will supply to all over the world, such as: Netherlands, Israel, Swaziland, Certainly, competitive price, suitable package and timely delivery will be assured as per customers' demands. We sincerely hope to build business relationship with you on the basis of mutual benefit and profit in the very near future. Warmly welcome to contact us and become our direct cooperators.
  • This is a very professional and honest Chinese supplier, from now on we fell in love with the Chinese manufacturing.
    5 Stars By Sophia from Portugal - 2017.09.16 13:44
    This supplier offers high quality but low price products, it is really a nice manufacturer and business partner.
    5 Stars By Ina from Lyon - 2018.09.29 13:24
    Write your message here and send it to us