continue to improve, to ensure product quality in line with market and customer standard requirements. Our company has a quality assurance system have been established for 4 Pole Smart Mcb , Electromagnetic Relay , Remote Control Smart Recloser , Our tenet is "Reasonable prices, economical production time and very best service" We hope to cooperate with much more shoppers for mutual enhancement and benefits.
Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai Detail:

Connection

The RST 25 can be connected as following in the installation diagram:
FlG1: Connection of the relay before operation.
When the relay is connected as in FIG 1, the three yellow LED’s L1,L2 and L3 light up when the power supply A1 phase L, the A2 Neutral, and the three phases”L1,”L2″and”L3″are properly connected.
If there is no under of overvoltage, phase failure of phase sequence, the green LED lights up,(terminals 11 and 14 are closed ) and the relay is ready for operation.
FIG2: Connection of the relay after operation.
When the relay is connected as in FIG 2,(the power supply Al phase L, the A2 Neutral are properly connected) after operation, the three phases”L1″,”L2″and”L3″are connected, andthere is no under of overvoltage, phase falure, phase sequence, the green LED lights up(terminals 11 and
14are closed) and the relay is ready for self retaining.
It is also possible to connect the power supply after operation in FIG2.
By both FIG’s 1 and 2, the terminal “PE”must be grounded.

Undervoltage
The desired undervoltage limit can be adjusted down to -25% UN.

Overvoltage
The desired overvoltage limit can be adjusted up to +25% UN.

Asymmetry
When adjusting over-and undervoltage limit, the asymmetric limit is also adjusted.

Time Delay
The switch off time can be adjusted by the potentiometer “Time’ Delay”from 0.1….5 seconds. With this function it is possible to adjust the time for the identification of the failure.

Contactor Control
If a phase fails during operation at load or one of the contacts of the contactor or circuit breaker is defect,(contact bounce or scorched contacts), RST 25 recognizes the failure, and also the feedback voltage, and switches off depending on the setting of “Time Delay”
The RST 25 controls the phase shift. If there is a phase failure during operation the angle from the feedback voltage is 30° and the RST 25 recognizes this failure.


Product detail pictures:

Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai detail pictures


Related Product Guide:

We can easily usually fulfill our respected customers with our very good top quality, very good price tag and excellent support due to we have been more expert and much more hard-working and do it in cost-effective way for Wholesale 3 Phase Timer Relay - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai , The product will supply to all over the world, such as: Norway, Congo, Czech Republic, With top quality products, great after-sales service and warranty policy, we win trust from many overseas partner, many good feedbacks witnessed our factory's growth. With full confidence and strength, welcome customers to contact and visit us for future relationship.
  • We are really happy to find such a manufacturer that ensuring product quality at the same time the price is very cheap.
    5 Stars By Marcy Real from Chile - 2018.09.21 11:01
    The company comply with the contract strict, a very reputable manufacturers, worthy a long-term cooperation.
    5 Stars By Lesley from Istanbul - 2018.04.25 16:46
    Write your message here and send it to us