Our primary objective is usually to offer our shoppers a serious and responsible small business relationship, offering personalized attention to all of them for 220v Smart Mccb , 63a Mcb , 24v Dc Contactor , You would not have any communication problem with us. We sincerely welcome prospects all around the globe to call us for business enterprise cooperation.
2020 Good Quality Switch-Disconnector - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai Detail:

Connection

The RST 25 can be connected as following in the installation diagram:
FlG1: Connection of the relay before operation.
When the relay is connected as in FIG 1, the three yellow LED’s L1,L2 and L3 light up when the power supply A1 phase L, the A2 Neutral, and the three phases”L1,”L2″and”L3″are properly connected.
If there is no under of overvoltage, phase failure of phase sequence, the green LED lights up,(terminals 11 and 14 are closed ) and the relay is ready for operation.
FIG2: Connection of the relay after operation.
When the relay is connected as in FIG 2,(the power supply Al phase L, the A2 Neutral are properly connected) after operation, the three phases”L1″,”L2″and”L3″are connected, andthere is no under of overvoltage, phase falure, phase sequence, the green LED lights up(terminals 11 and
14are closed) and the relay is ready for self retaining.
It is also possible to connect the power supply after operation in FIG2.
By both FIG’s 1 and 2, the terminal “PE”must be grounded.

Undervoltage
The desired undervoltage limit can be adjusted down to -25% UN.

Overvoltage
The desired overvoltage limit can be adjusted up to +25% UN.

Asymmetry
When adjusting over-and undervoltage limit, the asymmetric limit is also adjusted.

Time Delay
The switch off time can be adjusted by the potentiometer “Time’ Delay”from 0.1….5 seconds. With this function it is possible to adjust the time for the identification of the failure.

Contactor Control
If a phase fails during operation at load or one of the contacts of the contactor or circuit breaker is defect,(contact bounce or scorched contacts), RST 25 recognizes the failure, and also the feedback voltage, and switches off depending on the setting of “Time Delay”
The RST 25 controls the phase shift. If there is a phase failure during operation the angle from the feedback voltage is 30° and the RST 25 recognizes this failure.


Product detail pictures:

2020 Good Quality Switch-Disconnector - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai detail pictures


Related Product Guide:

We believe that prolonged time period partnership is really a result of top of the range, benefit added provider, prosperous knowledge and personal contact for 2020 Good Quality Switch-Disconnector - Wholesale hw-RST 25 Phase Failure Under Overvoltage Relay Sequence Relay – Hawai , The product will supply to all over the world, such as: Sao Paulo, Tanzania, Barbados, Providing Quality Products, Excellent Service, Competitive Prices and Prompt Delivery. Our products are selling well both in domestic and foreign markets. Our company is trying to be one important suppliers in China.
  • It is really lucky to meet such a good supplier, this is our most satisfied cooperation, I think we will work again!
    5 Stars By Kama from Seychelles - 2017.09.29 11:19
    Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
    5 Stars By Steven from Zambia - 2017.08.15 12:36
    Write your message here and send it to us