Specification
Standard | IEC/EN61009 |
Tripping Time | Type G 10ms delay TypeS 40ms delay-with selective disconnecting function |
Rated voltage (V) | 230/400V, 50/60Hz |
Rated currents (A) | 6,10,13,16,20,25,32,40,50,63A |
Rated tripping current In | 30,100,300,500mA |
Sensitivity | type A and type AC |
Rated short circuitstrenghtInc | 10000A |
Maximum back-up fuse Short circuit | In=25-63A 63A gL In=80A 80A gL |
Rated breaking capacity Im or Rated fault breaking capacity Im | In=25-40A 500A In=63A 630A In=80A 800A |
Endurance | electrical life>4,000operating cycles |
mechanical life>20,000 operating cycles | |
Frame size | 45mm |
Device height | 80mm |
Device width | 35mm(2MU),70mm(4MU) |
Mounting | on 35mm DIN rail according to EN 50022 |
Degree of protection built-in switch | IP40 |
Deg. of protection in moistureproof | IP54 |
Upper and lower terminals | open mouthed/lift terminals |
Terminal capacity | 1-25mm2 |
Busbar thickness | 0.8-2mm |
Tripping temperature | -25℃to + 40℃ |