Product Description | |||
Standard certifications | IEC60947-2 | ||
Item No. | M7125 | ||
Number of poles | 2,3,4 | ||
Electrical characteristics as per IEC60947-2 and EN60947-2 | |||
Rated current In | 16,20,25,32,40,50,63,80,100,125 | ||
Rated Operating Voltage,Ue | AC:415V | ||
Rated Insulated Voltage(Ui) | AC:800V | ||
Rated impulse withstand voltage,Uimpl | 8kV | ||
Types | M | H | |
Utimate breaking
capacity (kA rms Icu) |
220/240V | 25 | 38 |
380/400V | 15 | 25 | |
415V | 15 | 25 | |
550V | 10 | 10 | |
Rated service breaking capacity (kA rms Icu) |
220/240V | 15 | 18 |
380/400V | 7.5 | 15 | |
415V | 7.5 | 15 | |
550V | 5 | 5 | |
Protection function | Overload,short-circuit | ||
Type of trip unit | Thermal-magnetic | ||
Magnetic trip range | 400A | ||
Utilization category | A | ||
Endurance | Mechanical | 10000 operations | |
Electrical | 4000 operations | ||
Connection | Standard | Front connection | |
Mounting | Standard | Screw fixing | |
Dimentions(mm) |
Pole | ||
1 | 130x25×82 | ||
2 | 130x50×82 | ||
3 | 130×75×82 | ||
4 | 130×100×82 |