We're proud from the higher client fulfillment and wide acceptance due to our persistent pursuit of high quality both on product and service for Medium voltage , 400v Contact&Relay&Starter , Hv Isolating Switch , We are sincerely looking forward to cooperate with customers all over the world. We believe we can satisfy with you. We also warmly welcome customers to visit our factory and purchase our products.
Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai Detail:

Connection

The RST 25 can be connected as following in the installation diagram:
FlG1: Connection of the relay before operation.
When the relay is connected as in FIG 1, the three yellow LED’s L1,L2 and L3 light up when the power supply A1 phase L, the A2 Neutral, and the three phases”L1,”L2″and”L3″are properly connected.
If there is no under of overvoltage, phase failure of phase sequence, the green LED lights up,(terminals 11 and 14 are closed ) and the relay is ready for operation.
FIG2: Connection of the relay after operation.
When the relay is connected as in FIG 2,(the power supply Al phase L, the A2 Neutral are properly connected) after operation, the three phases”L1″,”L2″and”L3″are connected, andthere is no under of overvoltage, phase falure, phase sequence, the green LED lights up(terminals 11 and
14are closed) and the relay is ready for self retaining.
It is also possible to connect the power supply after operation in FIG2.
By both FIG’s 1 and 2, the terminal “PE”must be grounded.

Undervoltage
The desired undervoltage limit can be adjusted down to -25% UN.

Overvoltage
The desired overvoltage limit can be adjusted up to +25% UN.

Asymmetry
When adjusting over-and undervoltage limit, the asymmetric limit is also adjusted.

Time Delay
The switch off time can be adjusted by the potentiometer “Time’ Delay”from 0.1….5 seconds. With this function it is possible to adjust the time for the identification of the failure.

Contactor Control
If a phase fails during operation at load or one of the contacts of the contactor or circuit breaker is defect,(contact bounce or scorched contacts), RST 25 recognizes the failure, and also the feedback voltage, and switches off depending on the setting of “Time Delay”
The RST 25 controls the phase shift. If there is a phase failure during operation the angle from the feedback voltage is 30° and the RST 25 recognizes this failure.


Product detail pictures:

Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai detail pictures


Related Product Guide:

Our enhancement depends around the sophisticated devices ,exceptional talents and repeatedly strengthened technology forces for Good quality Solid State Safety Relay - Relay hw-RST 25 Phase Failure Under Overvoltage Sequence Relay – Hawai , The product will supply to all over the world, such as: Mongolia, Johannesburg, USA, We are in continuous service to our growing local and international clients. We aim to be worldwide leader in this industry and with this mind; it is our great pleasure to serve and bringing the highest satisfaction rates among the growing market.
  • Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
    5 Stars By Quyen Staten from Suriname - 2017.12.02 14:11
    This manufacturer can keep improving and perfecting products and service, it is in line with the rules of market competition, a competitive company.
    5 Stars By Klemen Hrovat from Malta - 2018.06.18 17:25
    Write your message here and send it to us